Common Daikin VRV fault codes for commercial systems (VRV III / VRV IV), what they mean, and whether it's safe to reset or needs a professional. Exact code sets can vary by model series — always confirm against your installation manual or ask us to check.
Reviewed by Lim Eng Yew (Ryder Lim), Founder & Managing Director, RY Lim Electrical & Aircond Engineering · Last reviewed: October 2026
| Code | Meaning | Common Cause | Action |
|---|---|---|---|
| Communication & System Codes (U-Series) | |||
| U0 | Shortage of refrigerant | Undercharge, faulty EEV, or sensor fault | Call Technician |
| U1 | Reversed or missing phase | Incorrect power phase wiring at the outdoor unit | Check First |
| U2 | Power supply fault | Voltage drop, faulty capacitor, or wiring fault | Check First |
| U3 | Check operation not executed | System commissioning/check run was not completed after installation or PCB replacement | Informational |
| U4 | Communication failure (indoor ↔ outdoor) | The most common Daikin VRV fault — usually a wiring or connector issue on the communication bus between units | Check First |
| U5 | Communication failure (indoor ↔ remote controller) | Loose or damaged remote controller wiring, or remote set to the wrong main/sub setting | Check First |
| U7 | Communication failure between outdoor units | Wiring fault on the outdoor-to-outdoor transmission line in multi-module systems | Check First |
| U8 | Communication failure between main and sub remote controllers | Both remotes set as "main", or a wiring fault between them | Informational |
| U9 | Communication failure with other units in the same system | A fault elsewhere in the refrigerant system — check the other indoor and outdoor units for their own codes | Check First |
| UA | System combination or setting error | Indoor/outdoor units not compatible, too many indoor units connected, or incorrect field settings | Call Technician |
| UE | Communication failure (indoor ↔ central controller) | Wiring or address fault between indoor units and the centralised controller | Check First |
| UF | System not set up / wiring–piping mismatch | Transmission wiring does not match the refrigerant piping, or the wiring check was not completed at commissioning | Call Technician |
| UH | System malfunction / auto-address failure | Transmission addresses could not be assigned — usually a wiring or setting issue after installation or modification | Call Technician |
| Indoor Unit Codes (A-Series) | |||
| A1 | Indoor unit PCB defect | Faulty indoor control board | Check First |
| A3 | Drain level control malfunction | Blocked drain, faulty float switch or drain pump | Informational |
| A6 | Fan motor lock or overload | Obstructed fan, worn bearing, or motor fault | Check First |
| A9 | Electronic expansion valve (EEV) malfunction | Faulty EEV coil or blocked valve | Check First |
| A0 | External protection device activated | A connected external safety device (e.g. fire alarm interlock) has tripped the unit | Check First |
| A7 | Swing flap motor malfunction | Louvre motor fault or obstructed flap | Informational |
| AJ | Capacity setting error (indoor) | Capacity adaptor or PCB setting does not match the indoor unit — often after a PCB replacement | Call Technician |
| Indoor Sensor Codes (C-Series) | |||
| C4 | Indoor heat exchanger liquid pipe thermistor fault | Sensor open/short circuit or loose connector | Check First |
| C5 | Indoor heat exchanger gas pipe thermistor fault | Sensor open/short circuit or loose connector | Check First |
| C9 | Indoor return (suction) air thermistor fault | Sensor open/short circuit or loose connector | Check First |
| CJ | Remote controller temperature sensor fault | Faulty sensor inside the wired remote controller | Informational |
| Outdoor Unit & Compressor Codes (E-Series) | |||
| E1 | Outdoor unit PCB defect | Faulty outdoor control board | Check First |
| E3 | High pressure switch (HPS) activated | Dirty condenser coil, blocked airflow, or overcharge | Call Technician |
| E4 | Low pressure switch (LPS) activated | Refrigerant undercharge or blocked piping | Call Technician |
| E5 | Compressor overheat or lock (inverter) | Refrigerant shortage, blocked piping, or inverter fault | Call Technician |
| E6 | Compressor overcurrent / locked rotor (standard compressor) | Electrical or mechanical compressor fault | Call Technician |
| E7 | Outdoor fan motor malfunction | Fan fails to run, stalls, or reports abnormal signal | Check First |
| E9 | Outdoor electronic expansion valve (EEV) malfunction | Faulty EEV coil, connector, or a stuck valve | Call Technician |
| Refrigerant Circuit, Sensor & Inverter Codes (F, H, J, L, P-Series) | |||
| F3 | Discharge pipe temperature too high | Low refrigerant, blocked condenser, or high ambient temperature | Call Technician |
| F6 | Refrigerant overcharge | Too much refrigerant charged, often after a top-up without weighing the charge | Call Technician |
| H3 | High pressure switch (HPS) itself faulty | Wiring break, connector failure, or switch defect | Check First |
| H9 | Outdoor air thermistor malfunction | Faulty sensor reading ambient temperature | Informational |
| J3 | Discharge pipe thermistor fault | Sensor open/short circuit or loose connector at the outdoor unit | Check First |
| J5 | Suction pipe thermistor fault | Sensor open/short circuit or loose connector at the outdoor unit | Check First |
| J6 | Outdoor heat exchanger thermistor fault | Sensor open/short circuit or loose connector | Check First |
| JA | High pressure sensor fault | Faulty pressure sensor or wiring | Call Technician |
| JC | Low pressure sensor fault | Faulty pressure sensor or wiring | Call Technician |
| L4 | Inverter heatsink overheating | Inverter cooling fin temperature too high — often airflow or fan related | Call Technician |
| L5 | Compressor / inverter fault (general) | Inverter module or compressor electrical fault | Call Technician |
| L8 | Inverter compressor overcurrent | Compressor overload, refrigerant problem, or inverter fault | Call Technician |
| L9 | Inverter compressor start-up failure | Compressor fails to start — inverter module, compressor or pressure-equalisation problem | Call Technician |
| LC | Communication failure between outdoor PCB and inverter PCB | Loose connector, wiring fault, or PCB defect inside the outdoor unit | Call Technician |
| P1 | Power supply imbalance / open phase (inverter) | Unbalanced or missing phase on the incoming supply | Check First |
| P4 | Inverter heatsink (radiation fin) thermistor fault | Sensor fault on the inverter module | Call Technician |
| PJ | Capacity setting mismatch (outdoor) | Inverter PCB capacity setting does not match the outdoor unit — usually after a PCB replacement | Call Technician |
U4 is a communication failure between the indoor and outdoor unit — the most common Daikin VRV fault. It's usually a wiring or connector issue on the communication bus rather than a major component failure, but it needs a technician to trace.
A single power cycle can clear a transient fault. But if the same code returns, stop resetting it — repeated cycling can mask the real fault or stress the compressor. Codes involving pressure switches, the compressor, or the inverter should be diagnosed by a technician, not repeatedly reset.
Yes. VRV III and VRV IV systems can assign slightly different meanings to the same code, and the exact fault detail is confirmed via the outdoor unit's diagnostic display or a service tool. This list covers the most common codes seen in the field; treat it as a starting point.
Send us a photo of the code and we'll help you understand it before booking a visit.